SEALING FITTINGS FOR HAZARDOUS LOCATIONS
COPPER FREE ALUMINUM
EYS SERIES
- Class I, Div. 1 & 2, group A, B, C, D.
Class II, Div. 1 & 2, group E, F, G.
Class lll, Div. 1 & 2. - Explosionproof
- Dust-ignitionproof
- Raintight
- Wet locations

APPLICATIONS:
- Restrict the passage of gases, vapors, liquids, dust and flames from one portion of the electrical installation to another at atmospheric pressure and normal ambient temperatures.
- Saline chamber test to paint according to ASTM B117.
- Paint adhesion test according to ASTM 3359.
- Resistance to mechanical impacts according to IK09 body, thanks to its design that does not have elements susceptible to breakage.
- NPT threaded for use with RIGID conduit, to ensure ground continuity.
- Vertical and Horizontal positions.
- 25% wire fill capacity
- Limit explosions to the sealed off enclosure.
- Limit precompression inconduit system.
MATERIAL:
- Diecast copper free aluminum. Robust and heavy duty.
FINISH:
- Electrostatic powder coating polyester polymerized by
oven minimum thickness 2 mils. Ensure a complete corrosion and UV rays protection grey color.
- Electrostatic powder coating polyester polymerized by
OPTIONAL:
- Galvanized removable close thread Nipple
INSTRUCTIONS:
- Are to be installed in each entrance within 18″ of a device that produce sparks, arcs or high temperature.
- The thickness of the sealing compound shall not be less than the trade size of conduit and in no case less than 5/8″.
Manufactured in compliance with:
- UL 886, UL 1203.
- CAN/CSA-C22.2 No. 30